Level 6 · Advanced HVAC control strategies

Coordinate the economizer, ventilation and occupancy clock

20 minutes · Advanced

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Separate ventilation demand from economizer cooling.
  • Interpret optimal start and stop against actual occupied conditions.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Two demands can move the same damper

An economizer admits additional outdoor air when conditions support cooling and modulates against a supply or mixed-air target. Demand-controlled ventilation (DCV) adjusts the occupancy-related ventilation requirement using a suitable indicator such as zone CO₂. Keep the design area's ventilation component, exhaust makeup and system minimums in view. A damper percentage is a position, while outdoor airflow depends on pressure and the intake path.

Check the temperature and moisture boundaries

For an ideal, well-mixed sensible case the mixed temperature is outdoor fraction × outdoor temperature plus return fraction × return temperature. The estimate becomes unreliable when the two temperatures are almost equal, the air stratifies or the sensor is misplaced. Dry-bulb-only enable and enthalpy-based enable make different judgments on humid days. Follow the installed sequence and calibrated measurements when interpreting eligibility.

Distinguish occupancy from recovery

Optimal start estimates how long the building needs to reach the occupied target by the scheduled time. Outdoor temperature, starting zone error and previously observed recovery can influence that estimate. Optimal stop allows earlier reduction of conditioning when the end-of-occupancy limits can still be met. Calendar exceptions, minimum ventilation during actual occupancy, protected uses and comfort limits constrain these strategies.

Morning transition
  1. Next occupied time and zone error
  2. Predicted warm-up or cool-down
  3. Appropriate recovery ventilation mode
  4. Occupied ventilation and temperature control
  5. Compare actual arrival condition

Normal operation

Example training conditions

  • In an ideal mixing example, equal mass flows of 50°F outdoor air and 74°F return air mix to about 62°F before the coils at similar specific heat.
  • The mixing calculation uses actual outdoor-air fraction. A damper command alone does not measure that fraction.

Worked service example

The fan starts early Monday, then the intake opens farther after people arrive.

Recorded field evidence · training example

  • Occupied start 08:00, recovery starts 07:05
  • At 08:00 the zone reaches its target
  • Outdoor 50°F, return 74°F, mixed 62°F under stable mixing

The early fan start is consistent with successful recovery. The three temperatures imply about 50% outdoor air for that interval. Review minimum ventilation and cooling demand separately to explain the later damper movement.

Field procedure

  1. Check calendar, occupied period and actual temperature at occupancy.
  2. Trend minimum ventilation demand, economizer eligibility, blade position and measured outside flow when available.
  3. Compare moisture and freeze limits with the approved sequence before changing minimums or start times.

Hands-on exercise

Compare two outdoor conditions with similar dry-bulb temperature and different humidity. Explain why an enthalpy-based changeover can select differently.

Psychrometric chart and cooling-coil test

At standard atmospheric pressure, compare two samples at the same dry bulb and coil surface temperature. Record a dry coil, then raise relative humidity until the model predicts condensation. The chart shows 20–100% RH in 20-point steps.

Psychrometric chart. Entering air 75°F at 35% relative humidity. Humidity ratio 6.4 grams per kilogram of dry air.01020304045556575859520%40%60%80%100%Water vapor (g/kg dry air)Dry-bulb temperature (°F)

Circle · entering air. Square · leaving air when within chart limits. Coil model uses 1,000 cfm and up to 18,000 Btu/h of cooling.

Dew point 45.5°F · entering enthalpy 25.0 Btu/lb dry air · leaving 58.3°F · condensate 0.00 lb/h

Unit 5 service call

The schedule changed. The equipment did not.

Trace a request to its active owner and prove who takes over on release. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. With outdoor air at 45°F and return air at 75°F, what is the ideal mixed temperature at 40% outdoor air?
2. A warm-up change brings the core zone to target by opening time but two perimeter rooms remain cold. What should be recorded before shortening warm-up further?
3. Two equal-density streams ideally mix to 64°F using outdoor air at 46°F and return air at 70°F. What percentage of the mixture is outdoor air?
4. An optimal-stop trial saves half an hour of cooling but a late-occupied zone exceeds its limit. What should the comparison include?
5. Cool outdoor air could meet the sensible load, but the project's economizer high-limit logic has disabled economizing. What should be examined before changing the enable?

Field takeaways

  • An outdoor damper can respond to cooling and to ventilation.
  • Assess start and stop using the measured condition at occupancy boundaries.

References and further reading