Airside commissioning
Accept a newly installed air handler and its exhaust interlock. Compare the installed setup with the project documents, correct discrepancies and record each retest.
Tenant fit-out · AHU-01 and EF-01
Each checkout starts from repeatable simulated conditions. Project settings, test evidence and open issues are saved on this device.
- Passed
- 0
- Failed
- 0
- Unverified
- 6
Engineering drawing, point list and sequence
Airside control drawing
- AHU-01 supply fan proof
- DDC proof timer
- EF-01 run output
- Exhaust motor and duct
On AHU-01, the heating output drives the actuator motor. The linkage moves the valve stem. The discharge sensor is downstream of the coil.
Sequence of operations
EF-01 starts on the first scan at or after 15 seconds of continuous AHU-01 supply fan proof. Loss of proof removes the start on the next scan. A new start requires the entire delay again. Use a scan interval of 1–5 seconds.
Approved point list
| Point | Function | BACnet address |
|---|---|---|
| AHU-01.DAT | Supply air temperature (SAT) | Device 11001 / AI 21 |
| AHU-01.HTG-VLV | Heating valve command | Device 11001 / AO 15 |
| AHU-01.HTG-VLV-FB | Heating actuator position | Device 11001 / AI 16 |
| AHU-01.SF-STS | Supply fan motor proof | Device 11001 / BI 7 |
| EF-01.EF-CMD | Exhaust fan request | Device 15001 / BO 3 |
| EF-01.EF-STS | Exhaust motor proof | Device 15001 / BI 4 |
Network checkout
The graphic must poll the AHU-01 discharge sensor’s commissioned device and object.
Sensor verification
At the discharge port, the displayed value must agree with the reference probe within 1.0 °F. Compare the probe and graphic before adjusting the simulated input trim.
Actuator calibration
Stroke the heating valve to both endpoints. Allow 75 simulated seconds and compare the motor feedback with the stem witness. Acceptance tolerance is ±3 percentage points.
Closed
Open
Functional performance
Run the installed exhaust logic through normal operation, interrupted proof and recovery. To correct the sequence, open the DDC editor, load the exhaust starter and save your wired diagram.
Restoration and handoff
Current heating valve hold · Automatic. Test an actuator endpoint, then release the hold before closing the project.
Commissioning report
The report includes the current disposition, acceptance criteria, measurements, test times and prior exceptions.
Preview report
BAS Bridge · Simulated commissioning report Airside tenant fit-out | CX-01 / Rev A | AHU-01 + EF-01 Disposition: Open for correction or verification. 0 passed | 0 failed | 6 unverified Heating valve operator hold: Released Point-to-point network binding — UNVERIFIED The graphic must poll the AHU-01 discharge sensor’s commissioned device and object. Discharge sensor verification — UNVERIFIED At the discharge port, the displayed value must agree with the reference probe within 1.0 °F. Heating valve · closed endpoint — UNVERIFIED With a 0% output, the motor and independent stem witness must both reach 0% within 3 percentage points. Heating valve · open endpoint — UNVERIFIED With a 100% output, the motor and independent stem witness must both reach 100% within 3 percentage points. Exhaust functional performance — UNVERIFIED Pass the start delay, interrupted proof, loss of proof, airflow and restart checks in sequence CX-01. Return actuator to automatic control — UNVERIFIED After an endpoint test, relinquish the operator command and verify automatic control.