Find the first check for a signal, symptom or unexpected reading.

7 field guides

Scale a 4–20 mA signal12 mA is halfway through a linear 4–20 mA signal. On a duct pressure transmitter set for 0–2.5 in. w.c., that’s 1.25 in. w.c.

Duct pressure training example

(12 − 4) ÷ 16 × 2.5 = 1.25 in. w.c. The transmitter is in one-way pressure mode. For another linear range, enter the engineering values assigned to 4 and 20 mA, including any nonzero low endpoint.

4–20 mA calculator

Use the transmitter’s engineering range and units.

1.25 in. w.c. · 50% of span

Distinguish span from offset

A transmitter is configured for 0–100 psi. Its current agrees with a reference at both test pressures, but the BAS shows 13 psi at 10 psi and 73 psi at 70 psi. Both errors are +3 psi. Check the input offset. If the BAS reads 10 and 82 psi instead, its displayed span is 72 psi for a 60 psi change. Check the configured endpoints before applying a trim. Verify the correction at a third pressure and record the as-left readings.

Compare the input with the field reading

The BAS shows 0.63 in. w.c.
Read the raw current at the controller. If it sees 12 mA, check its input mode and both scaling endpoints against the transmitter. If the raw reading differs from the measured current, check the input channel and loop wiring first.
The BAS shows 1.25 in. w.c., but the pressure looks wrong.
Compare an independent manometer across the same high and low taps with the fan at the same speed. If the readings disagree, check tubing, port assignment and transmitter zero. If they agree, investigate the air system at that operating condition.

Measuring the loop

Opening a live current loop interrupts its signal and can change equipment operation. Use an approved test point or suitable mA clamp. Follow the equipment isolation procedure before breaking the circuit. On the Veris PX3, confirm pressure mode, direction, output type and selected range.

Trace a pressure input on the heating skid

Compare the gauge, terminal current and controller’s engineering value to locate the first scaling error.

Identify a 10K thermistorA reading of 10,000 Ω at 77°F fits both curves in this table.
Nominal resistance at a stable sensor temperature
ReferenceBelimo 10k2Precon 10k3
32°F / 0°C32.65 kΩ29.49 kΩ
50°F / 10°C19.90 kΩ18.79 kΩ
68°F / 20°C12.49 kΩ12.26 kΩ
77°F / 25°C10.00 kΩ10.00 kΩ
86°F / 30°C8.06 kΩ8.19 kΩ
104°F / 40°C5.32 kΩ5.59 kΩ

Use the 50°F row

At 50°F, the 10k2 is nominally 19.90 kΩ and the Precon 10k3 is 18.79 kΩ, a difference of 1.11 kΩ. At 77°F that difference is zero. Get the sensor part number and compare its specified curve with the controller’s configured input curve.

Make the resistance reading comparable

Follow the controller and sensor isolation procedure. Verify the input is de-energized and disconnect the passive element as specified before using the ohmmeter. Put a reference thermometer at the sensing tip and wait for both to stabilize. Read resistance at the element so the cable and controller cannot affect the comparison.

The reading fits the part’s published tolerance at the measured temperature.
If the BAS temperature is still off, compare the isolated reading at the controller end, then check the configured curve. Include lead resistance and meter and thermometer accuracy.
Either curve could fit, or neither fits.
Confirm the part number and repeat at another stable temperature farther from 77°F. Use the tolerance for that part and temperature before identifying the element or calling it faulty.
Try the resistance sensor bench

Move the reference-temperature slider and compare the healthy reading with an open lead. This bench uses its own example 10 kΩ curve.

Trace an offline BACnet deviceAre the other points on this controller fresh? What about the controller beside it on the same segment?

Read the time of the last successful reply

Training example at 09:10. The supervisor polls every 30 seconds. VAV-4 room temperature last replied at 08:52. Its airflow and the neighboring VAV-5 both replied at 09:10. Start with the room-temperature object and its mapping.

How far does the stale data extend?

One point is stale. Other points on the same controller reply.
Check the device instance, object type, instance and property bound to the graphic. Use an authorized fresh read of that object. If it replies locally, trace the supervisor’s binding, subscription or cache. If the object reports unreliable input, check the sensor at the controller.
All points on one controller are stale. A peer on the same segment replies.
Check power and local controller status, then its port and connection. Compare its expected address with the project record. A live local display helps narrow the fault to the communication path.
Several peers went stale together.
From the supervisor, check the router and one device on a different segment. If that segment replies, inspect the affected trunk and its common power or wiring. If the router also fails to reply, work back toward its uplink and power.

When the room stays at 72°F

A change-of-value subscription may stay quiet while temperature is steady. Check the last successful device reply, point quality and subscription status. A new read returning the same 72°F proves that the device answered. A page refresh that repeats a cached value proves nothing about that link.

Trace the physical MS/TP trunk

Follow the two-wire RS-485 data pair along the documented daisy chain. Look for a spur, reversed pair or break at the first offline section. Mark the two physical ends. The EasyIO Neo CW guide specifies termination at both ends, typically 120 Ω. Check the installed controller instructions before fitting a resistor. Some end devices already provide switchable termination.

Locate the fail-safe bias

Bias resistors set the idle state of the data pair. Record which devices or end-of-line modules provide them. For example, the Johnson Controls TEC Series bulletin specifies bias and termination at each end. Use the wiring diagram for the installed product before changing any switches.

Read a BACnet/IP discovery record

Classic BACnet/IP commonly uses UDP 47808. A supervisor can send a Who-Is broadcast and receive an I-Am identifying the controller. Match the reported device instance and configured port to the project record. The temperature object still needs a fresh reading.

Compare devices on a simulated MS/TP trunk

Choose “Offline replacement.” Compare the replacement’s baud rate with its online peers, then choose the best verifying check.

VFD has a run command but the fan is stoppedAt the drive display, compare the selected command source, speed reference, actual output Hz and active inhibits with the effective BAS request.
Example linear speed reference with 0–60 Hz configured
Request0–10 V input4–20 mA inputTarget frequency
0%0 V4 mA0 Hz
50%5 V12 mA30 Hz
100%10 V20 mA60 Hz

Read the drive configuration

A separate run input and the drive’s permissives must both allow operation in this example. Compare the reference with actual output after the ramp. On a 4–20 mA input, 4 mA is a valid minimum. At 0 mA, check loop power, wiring and the configured signal-loss response. Minimum frequency and loss-of-signal action depend on the drive settings.

Two training calls

Run requested · Auto · 40 Hz reference · 0 Hz output · start inhibit active
On the example ABB ACH580, open Diagnostics → Active inhibits. The project sequence requires the outdoor-air damper’s open end switch before fan start. Follow the configured start-interlock input to that contact. Check blade position, then compare the end switch with the drive input. This locates a missing opening, missing proof or lost signal.
Run requested · Auto · 40 Hz output · airflow proof off
Check motor rotation with the guards in place using an approved observation point. If the motor is still, read output current on the drive display. Follow the drive and motor isolation procedure before tracing the output circuit. If it turns, verify the fan shaft turns too. A rotating motor and stationary wheel point to the belt or coupling. Isolate before opening guards.

If the fan wheel turns but proof stays off

Independent measurement shows little or no delivered airflow.
Verify fan rotation direction and check the inlet, filter and dampers along the discharge path.
Independent airflow is adequate.
Measure differential pressure at the proof-switch taps. Compare it with the specified pickup under the running condition. If pickup is met at the switch ports, compare contact state with the controller input. If pressure is low there, check tap locations and tubing against the duct reading.

Keep the original fault record

Before any reset, save the earliest fault code, time and recorded drive conditions. Keep protective interlocks in service. Use the installed model’s manual and the job sequence to identify its labels and the exact permissive.

Investigate an idle shop exhaust fan

Compare the winning BAS speed request with the drive’s selected reference, output frequency and the independent hood reading.

Low water ΔT across a coilWith 44°F water entering and 48°F leaving, compare the 4°F rise with the coil’s expected rise at the observed load and flow.

Check the measurement boundary

Training example · Take both readings at the same coil, upstream of any return-water mixing. Check both sensors against a common reference and sample them together after conditions settle. For cooling, leaving minus entering gives 48 − 44 = 4°F. For heating, entering minus leaving gives the water temperature drop.

Same 4°F rise, two next checks

Light load, discharge air at setpoint
Little heat may be entering the water. Check actual branch flow and valve position as demand falls. Compare the rise again during a known higher load before changing the balance.
Warm entering air, verified airflow, discharge air above setpoint
Measure flow through this coil and compare it with the design flow and actual valve travel. If flow is high for the load, check valve control and balancing. If flow is on target, compare entering and leaving air conditions and inspect for coil fouling or air bypass.

What the temperature difference tells you

At steady water flow, a smaller temperature change means less heat transfer. Compare the coil schedule or test-and-balance record with measured flow, entering-water temperature and current load. Plant-header temperatures include water from other branches and bypasses.

Work the hydronic valve case

A valve request rises while measured flow stays flat. Choose which pressure, mode and flow checks would distinguish the causes.

Read a hunting PID loopWhich moved first, the setpoint, the valve command, or the discharge-air temperature?
Training recording · cooling valve, fan running
TimeCooling command (%)Discharge air (°F)Setpoint (°F)
08:01655755
08:02825455
08:03465155
08:04185355
08:05305755

Follow one reversal

From 08:02 to 08:03 the cooling command falls from 82% to 46%, but discharge air keeps cooling from 54°F to 51°F. At 08:04 the air finally warms to 53°F. The target held at 55°F. That sequence fits a delayed response. These one-minute samples do not locate the delay in the actuator, coil or sensor.

If a different signal leads

The setpoint moves first
Trend the reset input, occupancy schedule and effective setpoint. Check whether the controller is following an intended target change.
An upstream condition moves first
Trend entering-air temperature, airflow and chilled-water supply beside the loop. If one changes before the discharge temperature and valve response, investigate that disturbance.

Before changing gains

Use aligned timestamps over several swings. Compare the discharge sensor with a reference, watch actual valve travel for sticking or delay, and check output limits, control direction and competing overrides. Reassess tuning under repeatable load once those checks agree.

Inspect A restless discharge loop

Move Inspect sample from 08:02 through 08:04. Compare the command reversal with the later rise in air temperature, then choose the finding the traces support.

Valve commanded open but the heating coil stays coldCheck which command won, then compare a local stem witness with branch flow and discharge temperature after the valve has had time to stroke.

Same AHU, same effective command

In both training runs, AHU-01 has 52°F mixed air, fan proof on, 6,538 cfm and a steady load. The BAS operator requests 100% open at priority 8. That command wins. Three simulated minutes later, compare the following readings against a 68°F discharge target. The BAS has motor feedback only. Stem position comes from a local witness.

Same graphic, different field evidence
ObservationStem stays shutStem opens
Motor-side BAS feedback100%100%
Stem witness at the valve0%100%
Measured coil branch flow0 gpm0 gpm
Distribution differential pressure10.9 psid0.0 psid
Local discharge probe52.6°F52.6°F

Where to check next

Motor indicates open, stem stays shut
Inspect the actuator-to-stem coupling and linkage against the valve’s stroke marks. Here the motor reached its endpoint while the driven stem stayed closed. If motor position is unavailable on your BAS, record it as unverified and witness both sides locally.
Stem reaches open, flow remains zero
Check the hot-water distribution pump’s run proof, actual output and differential at its test ports. Here the distribution differential is zero. If pressure is available at the branch instead, work toward the coil through the isolation valves and strainer.

Restore and prove heat delivery

After correction, release the test override to Auto and confirm the discharge loop regains control. With comparable entering air, airflow and load, verify branch flow, watch discharge rise toward target and check that the automatic output modulates as it settles.

Open the AHU heating-valve investigation

Start with the healthy reference stroke, then take the service call. Compare motor feedback, local stem travel and coil flow before choosing a correction.

Investigate the cold office wing · AHU-12