What you’ll learn
- Separate occurrence, acknowledgment and return to normal.
- Choose trend signals, time alignment and sample intervals that can resolve a fault.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Design an alarm for a meaningful operating condition
A fan An observation satisfying a defined criterion. A current switch proves current above its threshold. A duct switch proves pressure differential at its taps. alarm may require the fan to be commanded on, a startup delay to expire and proof to remain absent. An analog alarm may use a threshold, delay and differential to keep it from repeatedly entering and clearing near the boundary. Document enable conditions, severity, notification recipients and the action an operator should take. Acknowledgment records a response to the message. Return to normal records that the configured condition cleared.
Make a trend capable of answering the question
Trend the request, effective The effective instruction issued to a device. Compare it with actual travel, rotation or flow. , independent status, delivered variable and relevant permit. Select an interval short enough to capture the suspected transition. A one-minute interval can miss an eight-second dropout entirely. A change-of-value log avoids repeated identical values but its threshold can hide small movements. Compare controller clocks, sample age and actual timestamps before inferring which event came first.
Rebuild the timeline and test alternatives
Line up the first physical change, alarm delay, alarm timestamp, operator acknowledgment and later recovery. Compare a healthy cycle under similar demand. A single missing sample indicates an observation gap. Record plausible explanations that remain unresolved and the next signal or faster interval needed to separate them. Preserve the original trace when adjusting alarm settings or trend configuration.
- Run request remains on
- Measured proof drops
- Delay expires and alarm becomes active
- Operator acknowledges
- Proof returns and alarm clears
Normal operation
Example training conditions
- A fan starts at 07:30:00. Proof appears at 07:30:07, inside the configured 20-second delay. The command stays On and no proof-loss alarm is generated.
- Plot command and proof on the same clock with a sample interval short enough to distinguish the seven-second transition.
Worked service example
An operator believes acknowledging the alarm restarted the supply fan.
Recorded field evidence · training example
- 09:14:00 proof dropped with command still on
- 09:14:20 alarm active; 09:14:38 acknowledged
- 09:15:07 proof and duct airflow recovered
The trace puts acknowledgment 29 seconds before recovery, with no intervening recorded command change. Investigate local drive and protection history to explain the restart. The alarm actions alone do not establish causation.
Field procedure
- Preserve event timestamps and separate active, acknowledged and returned states.
- Align request, permission, proof and delivered measurements on the same time base.
- Compare with a healthy cycle and identify the shortest fault the chosen interval could miss.
Hands-on exercise
Inspect the trace for the first divergence between demand and the measured response. Compare its timing with the alarm delay.
Measure the continuous fan-proof delay
This synchronized event log includes the exact loss and alarm transitions. The fan remains commanded on. Times are seconds from 09:14:00.
Capture the fan request at the proof loss. Plot proof and alarm together and record the first lost proof and first annunciation.
Unit 11 service call
The equipment is running normally now. What happened overnight?
Separate the initiating event from its consequences and give the next shift a retest plan. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
AHU trends and alarm history
Open Trends and Alarms on the same AHU. Compare the retained command and proof signals with event onset and return times.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Alarm acknowledgment and physical recovery are distinct events.
- Choose sample timing for the duration of the behavior under investigation.
References and further reading
- Johnson Controls · Alarm and event management overview ↗
- Johnson Controls · Trend Automator application note ↗