Module examinationPass at 80%. 1. Which set of points gives the strongest evidence of a slipped outdoor-damper linkage?The icon is green and the tag includes OACommand and actuator agree, observed blade stays closed, and mixed-air temperature stays near returnCommand alone is high2. The asset name is correct but one sensor displays °C where the point list expects °F. Which check belongs first?Verify source object, configured units and display conversionReplace the sensorChange the plant's reset limits3. A fan loses proof for eight seconds between two one-minute samples. What does a flat trend establish?The fan ran continuouslyThe sampled endpoints matched; a shorter dropout can fit between themThe event is impossible4. A temporary P8 test ends. Which action allows the existing lower-priority schedule to regain control?Command zero at P8Write the current schedule value to P8 permanentlyRelinquish P8 to null5. P8 is null, P10 is 35% and P16 is 80%. What is the effective value?Answer (%)6. Proof drops at 14:01:07 and a continuous mismatch delay is 20 seconds. At what second past 14:01 would it first qualify if the mismatch persists?Answer (s)7. A BACnet binary output has active entries OFF at priority 8 and ON at priority 10; its relinquish default is OFF. What follows when priority 8 is released?All remaining entries are clearedPriority 10 takes effect and requests ONThe physical fan is proven ON immediately8. A trend records every 60 seconds. A proof drops for 9 seconds between consecutive samples. What additional evidence would best establish its duration?A daily average of run commandTime-stamped change-of-state events with synchronized clocksInterpolation between the two normal samplesSubmit assessmentApply this material in Unit 1Read the workstationApply this material in Unit 5Determine who owns the commandApply this material in Unit 11Work an intermittent call and hand it offReturn to Learning Center