Plant graphic says stopped while cooling continues

Chiller · Controls and communications · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

A stop indication appears on the supervisor, but building temperatures remain stable. Establish whether equipment stopped or the displayed evidence became unreliable.

Equipment and operating sequence

The chiller can continue under its local controller during a supervisory network interruption; this model retains its last valid remote setpoint.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 11:25: supervisor shows chiller STOPPED and leaving water 47°F.
  • Those points were last updated at 11:05; their quality flag is STALE.
  • Local panel at 11:25 reports RUNNING, leaving water 44°F, no active trip.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Compressor · case readings

Supervisor run indication Feedback
Stopped · Stale
Local run indication Feedback
Running

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Supervisor run indicationFeedback · CompressorStopped——StoppedStale—
Supervisor leaving waterReading · Evaporator47°F——Stale—
Local run indicationFeedback · CompressorRunning——Running——
Local leaving waterReading · Evaporator44°F————

Intake observations

  • 11:25: supervisor shows chiller STOPPED and leaving water 47°F.
  • Those points were last updated at 11:05; their quality flag is STALE.
  • Local panel at 11:25 reports RUNNING, leaving water 44°F, no active trip.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
ChillerLocal panel at 11:25 reports RUNNING, leaving water 44°F, no active trip.Intake recordUnreported11:25Unreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
Chiller11:25: supervisor shows chiller STOPPED and leaving water 47°F.Intake record
ChillerThose points were last updated at 11:05; their quality flag is STALE.Intake record
ChillerLocal panel at 11:25 reports RUNNING, leaving water 44°F, no active trip.Intake record

Field mentor