Work order CH-05

Condenser water warms despite maximum tower command

Chiller · VFDs and motors · Intermediate

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Condenser entering-water temperature is rising at unchanged load. Determine why additional tower command produces little response.

Equipment and operating sequence

Illustrative belt-driven open cooling tower. Tower approach means leaving tower water minus entering-air wet-bulb temperature; compare at similar flow and heat load.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 15:00: tower leaving water/chiller entering CW 94°F; tower entering water 104°F.
  • Entering-air wet bulb 76°F, independently verified; CW flow unchanged.
  • Tower fan command 100%; drive output 60 Hz; earlier comparable approach was 7°F.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Condenser system · case readings

Tower leaving water Reading
94 °F
Tower entering water Reading
104 °F
Tower fan Command
100 %
Tower drive output Feedback
60 Hz

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Tower leaving waterReading · Condenser system94°F————
Tower entering waterReading · Condenser system104°F————
Tower fanCommand · Condenser system100%100———
Tower drive outputFeedback · Condenser system60Hz—60——

Intake observations

  • 15:00: tower leaving water/chiller entering CW 94°F; tower entering water 104°F.
  • Entering-air wet bulb 76°F, independently verified; CW flow unchanged.
  • Tower fan command 100%; drive output 60 Hz; earlier comparable approach was 7°F.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
ChillerTower fan command 100%; drive output 60 Hz; earlier comparable approach was 7°F.Intake record

Field mentor