What you’ll learn
- Distinguish a drive enable, reference, output frequency and actual shaft response.
- Use the fan affinity laws to estimate the effect of a speed change.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Follow the signals in order
A variable frequency drive (VFD) controls motor excitation to vary speed. The run permission and speed reference can arrive through different paths. Read the active control source, enable, any drive limits, actual output frequency and A returned observation such as position or speed. Locate the pickup to see which part of the mechanism it represents. . Hz is electrical frequency. Shaft speed depends on motor type, poles, slip and mechanical transmission. An estimated speed register from the drive cannot reveal a broken belt by itself.
Calculate an expected change and check its assumptions
For the same centrifugal fan, comparable operating points, fixed geometry and essentially constant air density, flow varies with shaft speed, pressure with speed squared and shaft power with speed cubed. At 80% speed a first estimate is 80% flow, 64% pressure and 51.2% shaft power. A moving damper or changed static requirement moves the operating point. Drive input power also includes losses. Treat a large departure as a reason to measure shaft speed and system conditions.
- Run enable and speed reference
- Drive control source and limits
- Output frequency
- Motor and fan shaft speed
- Duct airflow and pressure
Normal operation
Example training conditions
- The drive is in remote automatic control with enable present and a 30 Hz speed reference. Its local output reads 30 Hz, a shaft tachometer confirms rotation and a hood records 650 cfm at the test outlet.
- Frequency describes the drive output. The last measurement tests delivery at the named outlet.
Worked service example
The cooling tower drive indicates normal speed, but heat rejection has fallen.
Recorded field evidence · training example
- Network speed reference 75%. Drive output 45 Hz on a 60 Hz base.
- Motor runs. Independent fan shaft tachometer near zero.
- Condenser-water leaving temperature rises under similar load.
The reference and electrical output agree. Inspect the mechanical path and independent tachometer evidence. Increasing frequency can obscure the failed transmission without restoring airflow.
Field procedure
- Verify drive source, enable, speed limits and feedback units.
- Compare drive frequency with independent motor and driven-shaft observations.
- Compare flow and pressure at matched system conditions and record departures from the predicted ratios.
Hands-on exercise
Reduce modeled shaft speed from 100% to 80% and compare predicted flow, pressure and shaft power. Explain why their percentages differ.
VFD and fan affinity laws
At full speed this fan delivers 6,000 cfm at 1.8 in. w.c. and 5 kW of shaft power. The illustration holds wheel diameter, air density and the system resistance curve constant.
Reduce speed to 50%. Calculate shaft power as a percentage of its full-speed value.
Unit 3 service call
The damper shows full travel. The room still has very little air.
Separate the electrical indication, physical movement and measured delivery. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Trace a cooling tower fan response
Compare tower drive output, shaft speed and condenser-water temperature. Decide where the response stops.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Trace enable and reference independently.
- Check installed system conditions before interpreting affinity-law predictions.