Level 2 · Motors and variable frequency drives

Read a drive from speed reference to delivered air

20 minutes · Intermediate

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Distinguish a drive enable, reference, output frequency and actual shaft response.
  • Use the fan affinity laws to estimate the effect of a speed change.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Follow the signals in order

A variable frequency drive (VFD) controls motor excitation to vary speed. The run permission and speed reference can arrive through different paths. Read the active control source, enable, any drive limits, actual output frequency and . Hz is electrical frequency. Shaft speed depends on motor type, poles, slip and mechanical transmission. An estimated speed register from the drive cannot reveal a broken belt by itself.

Calculate an expected change and check its assumptions

For the same centrifugal fan, comparable operating points, fixed geometry and essentially constant air density, flow varies with shaft speed, pressure with speed squared and shaft power with speed cubed. At 80% speed a first estimate is 80% flow, 64% pressure and 51.2% shaft power. A moving damper or changed static requirement moves the operating point. Drive input power also includes losses. Treat a large departure as a reason to measure shaft speed and system conditions.

A speed command reaching the duct
  1. Run enable and speed reference
  2. Drive control source and limits
  3. Output frequency
  4. Motor and fan shaft speed
  5. Duct airflow and pressure

Normal operation

Example training conditions

  • The drive is in remote automatic control with enable present and a 30 Hz speed reference. Its local output reads 30 Hz, a shaft tachometer confirms rotation and a hood records 650 cfm at the test outlet.
  • Frequency describes the drive output. The last measurement tests delivery at the named outlet.

Worked service example

The cooling tower drive indicates normal speed, but heat rejection has fallen.

Recorded field evidence · training example

  • Network speed reference 75%. Drive output 45 Hz on a 60 Hz base.
  • Motor runs. Independent fan shaft tachometer near zero.
  • Condenser-water leaving temperature rises under similar load.

The reference and electrical output agree. Inspect the mechanical path and independent tachometer evidence. Increasing frequency can obscure the failed transmission without restoring airflow.

Field procedure

  1. Verify drive source, enable, speed limits and feedback units.
  2. Compare drive frequency with independent motor and driven-shaft observations.
  3. Compare flow and pressure at matched system conditions and record departures from the predicted ratios.

Hands-on exercise

Reduce modeled shaft speed from 100% to 80% and compare predicted flow, pressure and shaft power. Explain why their percentages differ.

VFD and fan affinity laws

At full speed this fan delivers 6,000 cfm at 1.8 in. w.c. and 5 kW of shaft power. The illustration holds wheel diameter, air density and the system resistance curve constant.

0% speed100% speed
Airflow %Pressure %Shaft power %
6000 cfm · 1.80 in. w.c. · 5.000 kW shaft power

Reduce speed to 50%. Calculate shaft power as a percentage of its full-speed value.

Unit 3 service call

The damper shows full travel. The room still has very little air.

Separate the electrical indication, physical movement and measured delivery. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. At full speed a fan needs 16 kW of shaft power. Estimate shaft power at 50% speed under affinity-law assumptions.
2. A drive reports 50 Hz while an independent fan tachometer reads zero. What check best distinguishes a software display issue from a mechanical transmission fault?
3. Under the ideal fan laws at constant density on the same system curve, 2,400 cfm is delivered at full shaft speed. Estimate flow at 75% shaft speed.
4. The BAS speed request changes, but the drive stays at a fixed local keypad reference and indicates Hand. Which boundary should be verified?
5. Drive output frequency and shaft speed both increase while branch airflow remains low. Which pair best distinguishes duct restriction from a misreported flow pickup?

Field takeaways

  • Trace enable and reference independently.
  • Check installed system conditions before interpreting affinity-law predictions.

References and further reading

Technician handbook