Module examinationPass at 80%. 1. Valve position and stem travel reach 100%. The coil still delivers little heat. Which pair of readings best separates supply problems from a controls problem?Actuator serial number and schedule priority.Upstream water temperature and measured flow through the coil.Two copies of position command.2. A drive reports 50 Hz while an independent fan tachometer reads zero. What check best distinguishes a software display issue from a mechanical transmission fault?Increase the speed reference to maximum.Compare motor shaft and driven fan shaft motion under the same run condition.Change the engineering unit on the graphics page.3. A calibrated pickup gives 800 cfm at 0.16 in. w.c. At the same density, what flow corresponds to 0.04 in. w.c.?Answer (cfm)4. An actuator reports 100% travel. Its linkage is disconnected from the damper shaft. Which observation would disclose the failure?A second software display of the actuator feedbackA witnessed blade position and an independent airflow measurementA repeated 100% position request5. A return-air RH probe reads higher than a warmer reference brought from a service truck. Which observation makes the comparison meaningful?Both probes stabilized in the same air at matching temperature.Equal display precision.The maximum recorded CO₂ level that day.6. A linear 2–10 V position feedback signal reads 8 V. What position does the feedback channel report?Answer (%)7. A wall sensor and its adjacent reference both read 78°F. A second room location reads 72°F. Which test is most useful next?Check drafts, solar load and whether the installed location represents the occupied zone.Replace both instruments immediately.Subtract 6°F in the controller.8. At full speed a fan needs 16 kW of shaft power. Estimate shaft power at 50% speed under affinity-law assumptions.Answer (kW)9. A fan delivers 8,000 cfm at design speed. On the same ideal system curve, what flow is expected at 75% shaft speed?Answer (cfm)10. At comparable elevation the supply header is 41 psig and the return is 34 psig, measured simultaneously. What is the differential from supply to return?Answer (psi)11. A pump runs and differential pressure across a branch valve is high. Which observation directly tests whether water reaches the coil?An independent flow measurement through that coil branch.A larger differential reading at the same taps.The pump start command at the head end.Submit assessmentApply this material in Unit 3Verify sensors, actuators, and delivered outputReturn to Learning Center