What you’ll learn
- Separate actuator position, driven-element travel and delivered capacity.
- Identify evidence for a loose coupling, restricted flow or inadequate supply.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.The feedback pickoff has a location
A modulating actuator receives a position demand, drives through a finite stroke time and may return a position voltage. Mark where A returned observation such as position or speed. Locate the pickup to see which part of the mechanism it represents. originates. An actuator potentiometer can move with its motor while a loose shaft clamp leaves the damper blades still. A valve linkage can travel while a closed upstream isolation valve leaves the coil dry. Determine direction, full stroke time, mechanical stops and documented loss-of-power action for the installed assembly.
Make a measured step
In a simulator set two separated demands while holding the same operating mode and allowing full travel. Compare The effective instruction issued to a device. Compare it with actual travel, rotation or flow. , actuator feedback, blade shaft or valve stem, and a process result. With favorable outdoor air, opening an outdoor-air damper generally moves mixed-air temperature toward outdoor temperature. For a hot-water coil, seek water flow and a temperature rise across the airside with water temperature and airflow available. Equal percentages of valve stroke need not produce equal changes in flow.
What happens when actuator power is lost
A spring-return actuator stores mechanical energy during its powered stroke. On power loss, the spring moves the device toward its installed fail position. Fail-open and fail-closed describe a particular flow path. Identify the port and read the approved valve and linkage schedule. On a three-way valve, one path can open as the other closes. Loss of the control signal with power still present can have a different configured response. Inspect the specified behavior and observe the stem or blades during an authorized test.
- Analog demand
- Actuator shaft feedback
- Damper blade or valve stem
- Air or water response
Normal operation
Example training conditions
- During steady heating demand an effective 65% valve command produces 64% indicated position, visible stem movement and 3.5 gpm of hot water. Air temperature increases across the coil by 12°F.
- Observe each stage at the same load after the actuator has had time to travel.
Worked service example
The economizer commands outdoor air, but the mixed-air temperature barely changes.
Recorded field evidence · training example
- OA 48°F. Return 74°F. Mixed air remains 72°F.
- Command increases 20% to 80%. Actuator reports 79% after full stroke time.
- Actuator hub rotates. Blade shaft witness mark stays fixed.
The loss of motion lies between the actuator hub and blade shaft. The temperature evidence is consistent with little added outdoor air. Check the coupling and linkage before changing the economizer gain.
Field procedure
- Identify signal endpoints, direction, feedback source and stroke time.
- Compare physical travel at both ends of the coupling while the virtual command changes.
- Verify flow or temperature change under load and release the simulated override.
Hands-on exercise
Select Heating valve and note the current discharge temperature. Override HTG-VLV, compare its feedback and hot-water branch flow, diagnose the stuck valve and repeat the stroke after repair. Examine the DAT trend and release the test override to Auto.
AHU actuator stroke and process response
Command at least 75% for ten simulated seconds and record the missing travel. Identify the fault, repair the virtual heating valve, and repeat the stroke. Compare the temperature trend before and after repair. Release the test command after the verified stroke.
HW-GPM · measured branch flow 0.0 gpm. BLR-01.DIST-T · available supply water 145.9°F.
Inspect trend samples
| Time (s) | Command (%) | Travel (%) | Flow (gpm) | DAT (°F) |
|---|---|---|---|---|
| 60 | 0.0 | 0.0 | 0.0 | 66.5 |
Unit 3 service call
The damper shows full travel. The room still has very little air.
Separate the electrical indication, physical movement and measured delivery. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Inspect the connected AHU heating valve
Compare the effective valve request with actuator feedback, hot-water flow and discharge temperature. Use the AHU trends and relinquish any simulator test override after observing the response.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Trace feedback to its mechanical source.
- Verify actual process delivery after a stroke test.