Control and verification
PID tuning reference
Interpret a loop trend using target, process value, output, output limits and the physical response.
Symptoms and the first comparison
| Trend pattern | Field check |
|---|---|
| Output goes up while the error grows | Verify intended control direction, actuator orientation and the sensor used by the block. A heating and cooling process respond with opposite signs. |
| Output is limited and the error persists | Confirm load, available heating/cooling, flow, actuator travel and programmed limits. Additional gain cannot exceed an output limit. |
| Output moves smoothly and feedback sticks then jumps | Check valve or damper linkage, stiction and actuator stroke before changing tuning. |
| Process and output cycle with repeatable lag | Hold a repeatable load. Compare delay, stroke time, proportional settings and integral timing. Check for a moving reset target or a second competing loop. |
| Large output spikes from tiny input changes | Look for noisy feedback, derivative sensitivity, sampling interval or poor sensor placement. |
| Automatic control jumps after release from manual | Inspect integral tracking, output initialization, active priorities and the controller’s documented handoff behavior. |
Field example
A valve stays at 100% while verified discharge temperature is 8°F above cooling setpoint. Check chilled-water flow and temperature before increasing proportional gain.
Procedure
- Record the active setpoint, measured variable, output, units, limits, operating mode and starting parameters.
- Predict the process direction. Apply one repeatable disturbance in the simulator.
- Compare overshoot, settling, persistent offset and equipment cycling. Preserve the prior configuration and document any accepted change.
Practice and related lessons
Technical references
- Siemens · PID control block and parameters
- DOE · Commissioning for Federal Facilities
- Trane · High-Performance Sequences of Operation
- Caleffi idronics 32 · Troubleshooting Hydronic Systems
- ASHRAE · Guideline 36-2024 title, purpose and scope
- ASHRAE · Guideline 36-2021 addendum h, reset requests
- PNNL · Variable air volume systems