24 minutes · Advanced

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Read time order across a zone, AHU and plant.
  • Distinguish intentional reheat, valve leakage and competing loops.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Find who initiated the swing

Overlay zone error, the terminal flow target, damper, reheat output and upstream supply temperature. Watch which value changes first. A stable supply condition with an oscillating local points toward a local issue. Many terminals drifting together immediately after a supply reset points upstream. Choose a sample interval short enough to capture transitions and time-align the controllers.

Look for actual heat transfer

A cooling and a reheating terminal may be intentional during minimum ventilation or humidity control. Check the documented mode and air quantity. When heat is unexpected, compare effective valve command and stem travel with air temperatures immediately before and after the coil under steady flow. Account for sensor placement and other heat sources before attributing the temperature rise to that valve.

Separate upstream and terminal effects
  1. AHU supply condition
  2. VAV delivery vs target
  3. Reheat command and stem
  4. Temperature across coil
  5. Zone response

Normal operation

Example training conditions

  • Under a fixed occupied target and steady load, damper output and room temperature settle near a repeatable operating point. A brief load increase raises cooling demand and is followed by recovery.
  • Capture load, output and delivered response on one timeline before evaluating oscillation.

Worked service example

A perimeter zone runs warm while its AHU is cooling.

Recorded field evidence · training example

  • AHU supply 55°F and constant. Branch inlet 56°F, outlet 76°F.
  • Terminal reheat command 0%, actuator indicates shut.
  • At comparable flow, simulated isolation of the reheat water removes the temperature rise.

Water-side heat transfer explains the rise. Check valve seating and linkage before retuning the terminal temperature loop.

Field procedure

  1. Trend setpoint, demand, measured output and load together.
  2. Look for repeatable lead/lag and independent evidence at the suspected coil.
  3. Correct one cause and repeat under similar occupancy and supply conditions.

Hands-on exercise

Compare two histories and determine which change leads the other. Note where sampling limits the conclusion.

Localize a temperature swing across the terminal

One-minute samples were collected under steady airflow. Reheat output stayed at zero. Compare local temperatures and the shared AHU supply. These samples cannot establish event times between readings.

AHU supply air · °F
55560 min7 min
Terminal discharge air · °F
56760 min7 min
0 min · AHU supply air 55 °F · Terminal discharge air 56 °F

Capture AHU supply at the first terminal discharge rise. Then plot terminal discharge and zone temperature together and capture the first sampled rise in each.

Unit 8 service call

The discharge temperature swings above and below target.

Identify the earliest meaningful change and decide whether tuning is justified. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. Air enters the reheat coil at 56°F and leaves at 76°F. What temperature rise must the diagnosis explain?
2. Room temperature oscillates while a separate meter shows the hot-water supply temperature oscillating first. Which next trial isolates the effect?
3. Discharge temperature peaks at simulated seconds 25, 65 and 105. What is the approximate oscillation period?
4. All terminal zones begin oscillating immediately after AHU discharge swings. What should you examine first?
5. Both heating and cooling commands appear high. Which observation would verify simultaneous physical energy use?

Field takeaways

  • Assess the actual sequence and measured load.
  • Use leads and lags to choose the next measurement.

References and further reading

Technician handbook