Module examinationPass at 80%. 1. Air enters the reheat coil at 56°F and leaves at 76°F. What temperature rise must the diagnosis explain?Answer (°F)2. A cold discharge alarm appears only during warm-up. Two traces show cooling demand zero but the chilled-water valve stem partly open and supply air colder than mixed air. Which observation resolves the next uncertainty?Trend only the alarm countMeasure water-side flow or coil temperature change with the valve commanded closedIncrease the heating command immediately3. Local and colocated readings agree while several points are stale at the supervisor. Which comparison is most useful?A higher zone setpointTwo more views of the same cached graphicCurrent objects on both sides of the shared route4. A pump start was requested at 10:14:12, drive-ready occurred at 10:14:19 and flow proof at 10:14:25. How many seconds elapsed from request to flow proof?Answer (s)5. Safety trips at 12 s. Fan proof falls at 17 s. A proof alarm appears at 47 s. What delay follows the proof loss?Answer (s)6. A verified drive run signal and motor speed are normal, but delivered airflow is zero. Which test most directly separates a mechanical delivery fault from a bad BAS flow indication?A fresh fan commandThe occupied scheduleAn independent duct airflow measurement7. All terminal zones begin oscillating immediately after AHU discharge swings. What should you examine first?The common AHU loop and sensor historyEvery proportional gain independentlyEvery terminal's room schedule8. At 10:12:30, the last supervisory update was 10:08:00. What is the sample age?Answer (s)Submit assessmentApply this material in Unit 11Work an intermittent call and hand it offApply this material in Unit 9Diagnose network and data-quality faultsApply this material in Unit 8Diagnose with trends before changing a control loopReturn to Learning Center