What you’ll learn
- Identify the controlled variable, target and manipulated output.
- Predict how a feedback loop responds to a load change and to sensor bias.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.What returns to the controller?
A scheduled 40% outdoor-air damper The effective instruction issued to a device. Compare it with actual travel, rotation or flow. is open loop with respect to outdoor airflow when no measured airflow adjusts that command. The damper actuator can still have an internal position loop. An airflow controller is closed loop when it compares measured airflow with a target and adjusts the damper to reduce the difference. Identify the variable at each level before deciding whether a loop is open or closed.
Check the response direction before the gain
For the usual example cooling valve, an increase in cooling flow should lower discharge temperature under load. Look at both the initial output move and the delayed temperature response. A reversed actuator linkage, a sensor ahead of the coil or unavailable chilled water can all make a correctly computed request appear ineffective. Choose a separate measurement at each boundary before changing the program.
A loop can control the wrong reading accurately
Suppose a discharge-air controller modulates a cooling valve to hold 55°F. Warmer entering air adds load. With valid A returned observation such as position or speed. Locate the pickup to see which part of the mechanism it represents. the controller can increase cooling output until discharge temperature recovers, provided chilled water and coil capacity are available. If the sensor reads 4°F too warm, the controller may cool actual air to about 51°F while its own display sits on target. Compare a stable, co-located independent reading before altering tuning.
- 55°F target
- Compare with DAT
- Adjust cooling valve
- Coil changes air temperature
- DAT sensor returns measurement
Normal operation
Example training conditions
- With a steady cooling load, target discharge air is 58°F, measured discharge is 58.2°F and the cooling valve is at 41%. An added load raises discharge to 60°F; the loop opens the valve and discharge returns toward 58°F.
- A fixed valve command could stay at 41% through that change. Feedback provides a way to correct the resulting temperature error.
Worked service example
Occupants report cold drafts while discharge temperature tracks its target.
Recorded field evidence · training example
- DAT setpoint 55°F. Indicated DAT 55°F.
- Co-located reference 51°F after settling.
- Cooling valve 62% with chilled water available.
The displayed error is zero while field temperature is 4°F low. Verify the reference and placement, then investigate the sensor chain. A different loop gain would still regulate using the biased input.
Field procedure
- Name the measured variable, its units and the active target.
- Trace the output to the physical process and identify expected response direction.
- Compare feedback with an independent reference at the same location and load.
Hands-on exercise
Use the loop tool to change its target. Identify the response that moves first and the measured variable that follows.
Duct static PID bench
Record a P-only offset by advancing 60 seconds at the starting load. Keep that target and load, add integral action, then hold pressure within 0.06 in. w.c. for ten samples with the output inside its limits. Try an integral gain of 1 and allow several minutes for recovery.
P 0.00 · I 0.00 · D 0.00 percentage points of output
Unit 8 service call
The discharge temperature swings above and below target.
Identify the earliest meaningful change and decide whether tuning is justified. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Observe a discharge-air loop
Select discharge-air temperature. Change one control setting, run the same load condition and compare target, output and measured temperature.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Name the controlled variable before labeling a loop.
- Check measurement accuracy and process capacity before tuning.