Level 2 · Direct digital control

Follow an open loop and a closed loop

18 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Identify the controlled variable, target and manipulated output.
  • Predict how a feedback loop responds to a load change and to sensor bias.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

What returns to the controller?

A scheduled 40% outdoor-air damper is open loop with respect to outdoor airflow when no measured airflow adjusts that command. The damper actuator can still have an internal position loop. An airflow controller is closed loop when it compares measured airflow with a target and adjusts the damper to reduce the difference. Identify the variable at each level before deciding whether a loop is open or closed.

Check the response direction before the gain

For the usual example cooling valve, an increase in cooling flow should lower discharge temperature under load. Look at both the initial output move and the delayed temperature response. A reversed actuator linkage, a sensor ahead of the coil or unavailable chilled water can all make a correctly computed request appear ineffective. Choose a separate measurement at each boundary before changing the program.

A loop can control the wrong reading accurately

Suppose a discharge-air controller modulates a cooling valve to hold 55°F. Warmer entering air adds load. With valid the controller can increase cooling output until discharge temperature recovers, provided chilled water and coil capacity are available. If the sensor reads 4°F too warm, the controller may cool actual air to about 51°F while its own display sits on target. Compare a stable, co-located independent reading before altering tuning.

Discharge-air temperature feedback
  1. 55°F target
  2. Compare with DAT
  3. Adjust cooling valve
  4. Coil changes air temperature
  5. DAT sensor returns measurement

Normal operation

Example training conditions

  • With a steady cooling load, target discharge air is 58°F, measured discharge is 58.2°F and the cooling valve is at 41%. An added load raises discharge to 60°F; the loop opens the valve and discharge returns toward 58°F.
  • A fixed valve command could stay at 41% through that change. Feedback provides a way to correct the resulting temperature error.

Worked service example

Occupants report cold drafts while discharge temperature tracks its target.

Recorded field evidence · training example

  • DAT setpoint 55°F. Indicated DAT 55°F.
  • Co-located reference 51°F after settling.
  • Cooling valve 62% with chilled water available.

The displayed error is zero while field temperature is 4°F low. Verify the reference and placement, then investigate the sensor chain. A different loop gain would still regulate using the biased input.

Field procedure

  1. Name the measured variable, its units and the active target.
  2. Trace the output to the physical process and identify expected response direction.
  3. Compare feedback with an independent reference at the same location and load.

Hands-on exercise

Use the loop tool to change its target. Identify the response that moves first and the measured variable that follows.

Duct static PID bench

Record a P-only offset by advancing 60 seconds at the starting load. Keep that target and load, add integral action, then hold pressure within 0.06 in. w.c. for ten samples with the output inside its limits. Try an integral gain of 1 and allow several minutes for recovery.

0 s · pressure 0.854 in. w.c. · error 0.346 in. w.c. · fan output 65.0%

P 0.00 · I 0.00 · D 0.00 percentage points of output

0 s0 s
Pressure (in. w.c.)Target (in. w.c.)

Unit 8 service call

The discharge temperature swings above and below target.

Identify the earliest meaningful change and decide whether tuning is justified. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. A position-servo damper holds 40% on a fixed schedule. Which statement applies to outdoor airflow?
2. Duct pressure is below its target. In the example loop increasing supply-fan speed raises pressure. Which initial output change reduces the error?
3. During a heating test the target is 122°F, the measured water temperature is 116°F and error is defined as target minus measurement. What is the signed error?
4. A damper follows a time schedule and outdoor flow falls when wind shifts. What feedback would close a loop around the intended ventilation quantity?
5. A cooling loop holds its indicated discharge temperature at 58°F. Its sensor consistently reads 3°F above the air temperature. Estimate the actual temperature.

Field takeaways

  • Name the controlled variable before labeling a loop.
  • Check measurement accuracy and process capacity before tuning.