Identify likely point roles, equipment and units while reading project drawings and graphics.

Typical drawing and point-list abbreviations

Typical drawing and point-list abbreviations
AbbreviationMeaning and example
BAS / BMSBuilding automation system / building management system. Project documents define the installed scope.
DDCDirect digital control. The control program samples inputs and updates outputs.
AI / AOAnalog input / output. An example pair is a duct static transmitter and a fan speed reference.
BI / BO, DI / DOBinary or digital input / output. A run-proof contact and start relay are examples.
AHU / RTU / FCUAir-handling unit / rooftop unit / fan-coil unit.
VAV / DOASVariable air volume / dedicated outdoor air system.
OAT / MAT / RATOutdoor-, mixed- and return-air temperature. Record the sampling location.
DAT / SATDischarge- and supply-air temperature. Their locations can differ across coil, fan and terminal equipment.
DP / DSPDifferential pressure / duct static pressure. Record both tap locations.
CHWS / CHWRChilled-water supply / return. Verify flow direction on the drawings.
HWS / HWRHeating-water supply / return in this context. Confirm the system prefix on the job.
SP / PV / CVSetpoint / process variable / control variable. Verify local block naming.
CMD / FB / STSCommand / feedback / status. Inspect the source for each.
VFD / HOAVariable frequency drive / hand-off-auto selector.
CFM / gpmCubic feet per minute / U.S. gallons per minute in this handbook.

Field example

AHU-01.SF-SPD-FB identifies an air-handler supply fan speed feedback point in this simulator. Trace the point source before using it as proof of shaft speed.