Level 4 · Building automation networking

Read a network riser from the workstation to the last controller

19 minutes · Intermediate

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Distinguish an Ethernet/IP path from the serial segment on a riser.
  • Use address, time and device scope to select the next non-disruptive check.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Draw the reporting path

A network carries messages between devices. An Ethernet switch forwards local network frames among its ports. Internet Protocol (IP) addresses identify interfaces for IP communication. BACnet is a building automation communications protocol. A BACnet router can join a BACnet/IP side to a BACnet MS/TP serial side. A local field controller may keep regulating its equipment while the workstation no longer receives its reports.

Read an IPv4 subnet

A groups IP addresses under a shared network prefix. In this fictional , 192.0.2.10/24 and 192.0.2.40/24 belong to the same IP subnet. The slash length 24 means the first 24 bits are the prefix, equivalent to a 255.255.255.0 mask. A host at 198.51.100.40/24 belongs to a different subnet. An IP router connects IP subnets; a BACnet router forwards BACnet messages between BACnet networks. These roles can reside in different devices.

Trace the serial segment

MS/TP stands for Multidrop Serial Bus/Token Passing. Older drawings may use the former name Master-Slave/Token-Passing. Its devices share a serial bus over an electrical layer. Two signal conductors carry a differential voltage. Token passing coordinates which eligible device may transmit. On this training trunk, every device uses the same signaling rate (baud) and a unique local station address. A BACnet device instance identifies a device at the BACnet system level. A serial station number is not an IP address.

Know what the drawing can establish

On the specified daisy-chain segment, cable runs from one device to the next. Termination at the prescribed ends controls signal reflections. Biasing establishes a defined idle electrical state when transmitters release the bus. Manufacturer documentation determines cable construction, resistor arrangements, bias locations, grounding and repeaters. Read the installed drawing and settings record before any authorized physical work.

Fictional riser from workstation to the end of a serial segment
  1. Workstation · Ethernet
  2. BACnet router
  3. First serial station
  4. End of segment

Normal operation

Example training conditions

  • Fictional office drawing. Workstation 192.0.2.10/24 and the BACnet router’s IP interface 192.0.2.40/24 share an Ethernet switch.
  • On the serial side, stations 5, 6 and 7 send fresh timestamps at their configured common baud rate. A controller’s local temperature agrees with its fresh supervisory reading within instrument uncertainty.

Worked service example

Two adjacent rooms stop updating on the workstation while a neighboring room remains current.

Recorded field evidence · training example

  • Router IP-side status and the first serial station still update at 11:10.
  • The next two serial devices last reported at 10:52. A local indication on the last device changes at 11:10.
  • The drawing places both stale devices after the last fresh station on one physical segment.

The first fresh serial station demonstrates a working reporting path as far as that device. Both stale stations share a downstream boundary. Compare the installed riser, device power and non-disruptive communication status at that boundary. Local changes show continued local measurement. These observations alone cannot distinguish an open cable, lost segment power or another communication fault.

Terms in this lesson
Riser
A drawing showing communications segments, device relationships and connections across the building.
Subnet
The IP addresses that share a defined network prefix.
RS-485
A balanced electrical signaling layer used by many serial field buses.
Topology
The physical or logical arrangement of a network.

Hands-on exercise

Inspect four stops on a second fictional riser. Identify the smallest boundary shared by the stale reports.

Predict before inspection

If a common IP path fails completely, which pattern would you expect under the assumptions in this drawing?

Knowledge check

Pass at 80%.

1. How many leading bits define the prefix in an IPv4 /24 network?
2. One serial device is configured for a different fixed baud rate. What would you expect?
3. Which interface shares the IP subnet with 192.0.2.25/24?
4. What is the design purpose of prescribed end termination on this RS-485 segment?
5. Yesterday a station went stale and its neighbors stayed fresh. Which action best preserves evidence?

Field takeaways

  • Record the last fresh device, the first stale device, their physical order and the time. Preserve the working segment while localizing the failure.

References and further reading