Level 4 · Commissioning and documentation

Prove the input from terminal to graphic

18 minutes · Intermediate

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Trace one input from its field tag to its displayed object.
  • Separate span, offset and point-mapping errors using independent measurements.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Work outward from a known input

Find the sensor tag, physical input channel, signal range, units and object identifier in the approved points list. Record the as-found value. Apply a known simulated input, watch the raw channel and follow the change to the controller value and operator graphic. If a different zone responds, the wiring or binding can be wrong even when the displayed number looks reasonable.

Test more than one condition

A single midscale reading can conceal a reversed range or a fixed display value. Use low and high references, then an intermediate point to check linearity. For a temperature sensor, use its specified curve and a colocated reference allowed to stabilize. Record reference accuracy and the project tolerance before adjusting calibration. A corrected display offset cannot repair a wrong sensor curve.

One physical input, four checkpoints
  1. Device tag and reference
  2. Controller terminal and raw signal
  3. Scaled object and units
  4. Graphic with matching timestamp

Normal operation

Example training conditions

  • With the project input range at 4–20 mA for 0–100 psi, a 12 mA simulator at the identified input produces 50 psi at the local controller and at the matching graphic tag.
  • Signal injection checks the channel and mapping. Reconnect the original sensor and verify its measured process before closeout.

Worked service example

Two duct transmitters pass a visual check at zero pressure.

Recorded field evidence · training example

  • Transmitter span 0–2 in. w.c. at 4–20 mA.
  • At 12 mA the local reference is 1.00 in. w.c.
  • AI-3 shows 1.00. The graphic reads 0.00 and changes when AI-4 is tested.

AI-3 scales correctly at the tested condition. The graphic responds to another input. Trace its binding before calibrating either device.

Field procedure

  1. Match the terminal and object to the approved submittal.
  2. Capture low and high references with time and units.
  3. Check an intermediate reading, compare error with tolerance, then restore service.

Hands-on exercise

Run the low and high point checks and compare both readings to the expected endpoints.

Two-endpoint actuator checkout

The approved submittal maps 2–10 V to 0–100% travel. At each endpoint compare the BAS request with the actuator terminal voltage and shaft witness mark. Return the point to automatic control.

Terminal voltage 4.80 V · shaft witness 35% after travelRecorded positions · None

Record the low and high terminal readings and return the output to automatic control.

Unit 10 service call

A checkout point moves in the wrong direction under load.

Leave a reproducible point-to-point, functional and restoration record. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%. Every safety item must also pass.

1. For a linear 4–20 mA, 0–2 in. w.c. transmitter, what should 16 mA indicate?
2. A technician injects a test voltage at a controller and the correct BAS graphic tracks it. Which part of the installed measurement chain still needs an independent check?
3. A fictional input scales 2–10 V to 0–80°F. At a simulated 5 V input what engineering temperature should appear?
4. AI-3 changes correctly but the graphic follows AI-4. What should you check first?
5. After signal injection, which action belongs in a completed input checkout? · Required for safety

Field takeaways

  • Prove point identity and range separately.
  • Keep the reference, displayed response and acceptance tolerance together.

References and further reading

Technician handbook