HVAC Equipment Sequences

Follow a call for conditioning from scheduled demand through physical delivery at the zone and plant.

Module examination

Pass at 80%.

1. Cooling-tower water enters at 94°F and leaves at 83°F. Entering air wet bulb is 76°F. Calculate approach.
2. Chilled-water flow is proven and condenser flow reads zero. Which next check follows the heat rejection path?
3. At 100% damper position a VAV box delivers only half its flow target. Which check is most discriminating?
4. What observation establishes that a heat pump is delivering heat to its indoor airstream?
5. Plain water flows at 80 gpm through a heating plant with an 8°F supply-to-return difference. Estimate transferred heat.
6. A water coil receives 14 gpm. Its entering and leaving water temperatures are 152°F and 139°F. Estimate heat released using 500 × gpm × ΔT.
7. With a fan request on, motor proof on and zero measured airflow, which check best separates drive operation from air delivery?
8. An RTU blower is proven and outdoor-air cooling is insufficient. A compressor command is on, compressor proof stays off and discharge temperature stays near mixed air. Where should diagnosis continue?
9. An unoccupied unit starts during a cold night. Which information should you compare before calling it a schedule fault?