What you’ll learn
- Trace boiler and water-cooled chiller startup through pumps and protection.
- Use flow and temperature difference to assess delivered load.
Before you start · 3 related lessons
0 of 3 prerequisites demonstrated. You can open this lesson at any time.Build a permissive chain for each machine
A plant request can open isolation valves, start distribution or primary pumps and wait for proven circulation before enabling a boiler or chiller. A water-cooled chiller also needs its condenser path available for heat rejection. The tower fan can modulate to a water temperature target. The local machine controller still owns its operating limits. Use the approved sequence to determine what circulation must already exist at each stage.
Read a cooling tower against the entering wet bulb
Range is hot water entering the tower minus cold water leaving. Approach is cold water leaving minus the wet-bulb temperature of air entering the tower. At 95°F hot water, 85°F cold water and 77°F entering wet bulb, range is 10°F and approach is 8°F. Compare at similar water flow, load and wet bulb. If the tower fan is commanded high with a poor approach, check actual fan operation and airflow before deciding that the tower surface has fouled.
Find where the heat went
At ordinary HVAC temperatures the water-side rate for plain water is approximately 500 × gpm × temperature difference in °F, in Btu/h. Use return minus supply for cooling delivered, supply minus return for heating. Glycol mixtures require their actual density and specific heat. A high boiler temperature with negligible distribution flow can satisfy the boiler sensor while remote coils remain cold.
Separate stage demand from safety shutdown
Two boilers may rotate lead duty and add lag capacity only after a sustained supply-temperature deficit with the lead near useful capacity. A standby unit may also start on a lead failure if the project permits it. An active flame safeguard, low-water trip or chiller high-pressure limit calls for qualified investigation. Document the lockout and the last valid flow and temperature readings before considering any change to staging.
- Cooling demand persists
- Water valves open and pumps operate
- Evaporator and condenser flow proven
- Chiller starts under local limits
- Load reaches water and tower
Normal operation
Example training conditions
- Under steady cooling demand a water-cooled chiller has evaporator and condenser flow proven before compressor start. Example chilled water enters at 54°F and leaves at 44°F.
- The condenser circuit carries the rejected heat toward the cooling tower. A supply temperature alone cannot establish the heat transfer rate.
Worked service example
The lead chiller is proven on but the operator questions its delivered capacity.
Recorded field evidence · training example
- Evaporator flow 120 gpm of plain water
- Chilled-water return 54°F, supply 46°F
- Both temperatures are simultaneous and independently checked
The water side carries approximately 480,000 Btu/h, or 40 refrigeration tons. This operating load can be compared with demand, while nameplate capacity describes a rating condition.
Field procedure
- Read the demand, isolation valves, pump proofs and lockout history in time order.
- Confirm both water paths and the location and units of each measured temperature.
- Calculate transferred load, then compare lag demand and actual stage performance.
Hands-on exercise
Represent a chiller enable with independent evaporator and condenser flow permissions. Predict the outcome with one path unavailable.
Boolean permissive circuit
Use AND to prove a start with both requests. Record it, then trip the safety with the requests still present and prove the output drops.
Unit 7 service call
The supply header is hot, but the perimeter is cold.
Compare the header, healthy branch and affected coil under the same load. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
CH-01 chilled-water plant
Inspect the evaporator flow and condenser flow independently, then correlate them with compressor proof and leaving-water temperature.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Track heat transfer across each circuit using paired, contemporaneous readings.
- Capacity staging and local safety trips have different evidence and recovery paths.
References and further reading
- Trane · Condenser water system savings ↗
- U.S. Department of Energy · Energy-efficient commercial boilers ↗
- ASHRAE · Guideline 36-2018 addendum x, chilled-water plant control ↗
- SPX Cooling Technologies · Cooling tower range and approach ↗