What you’ll learn
- Identify which water circuit serves the occupied building.
- Compare evaporator and condenser measurements under load.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.What the equipment does
A chiller removes heat from water so that chilled water can cool air at distant coils. In a water-cooled vapor-compression chiller, refrigerant absorbs heat in the The heat exchanger where refrigerant absorbs heat as it evaporates. , the compressor raises refrigerant pressure and the condenser transfers heat to a second water circuit. An expansion device reduces refrigerant pressure before the evaporator.
Follow the physical path
Warm chilled-water return enters the evaporator and cooler chilled water leaves for the building. Separate The separate water loop carrying rejected heat to the tower. arrives from the cooling tower, picks up rejected heat and returns to the tower warmer. Under steady load the condenser rejects both the heat lifted from the building loop and the energy supplied to the compressor.
Chilled-water circuit
Refrigerant circuit · repeats to evaporator
Return header · Water from the branches comes back here. Compare temperatures and flow with the supply.
Normal operation
Example training conditions
- With verified water flow and a cooling load, chilled water enters at 54°F and leaves at 44°F.
- In a separate circuit, condenser water enters at 81°F and leaves for the tower at 91°F.
Worked service example
The operator sees 91°F leaving water and thinks the building receives hot water instead of chilled water.
Recorded field evidence · training example
- 91°F is tagged leaving condenser water.
- Leaving evaporator water reads 44°F locally and at the plant.
- The room complaint has no zone-side airflow or water-flow measurements.
The warm value belongs to heat rejection. The measured chilled supply is cool at the plant. Trace that circuit to the affected coil and check delivery before blaming the chiller.
Terms in this lesson
- Evaporator
- The heat exchanger where refrigerant absorbs heat as it evaporates.
- Condenser water
- The separate water loop carrying rejected heat to the tower.
Hands-on exercise
Identify the useful cooling and heat rejection paths during steady operation.
Predict before inspection
Standalone simulator · free practice
Inspect CH-01
Locate the evaporator and condenser water paths and compare their temperatures.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Write the circuit name next to every entering and leaving water reading.