Level 1 · Commercial HVAC equipment anatomy

Read a cooling tower’s heat rejection

12 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Trace condenser water through a tower.
  • Calculate cooling range and compare outlet temperature with outdoor wet-bulb.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

What the equipment does

A cooling tower transfers heat from warm condenser water to outdoor air. In an evaporative tower a small fraction of the water evaporates. Air flows over wetted surfaces called fill, and cooler water collects in a basin. A fan can increase airflow through the tower.

Follow the physical path

Trace heated water from the chiller condenser to the tower inlet, across the fill and back toward the condenser. Outdoor temperature describes the cooling effect available through evaporation. The cold-water outlet normally stays above the entering-air wet-bulb under useful load. Range is hot inlet minus cold outlet. is cold outlet minus entering-air wet-bulb.

Follow the equipment pathsSelect a component to inspect its function.

Condenser-water circuit

Tower air · induced-draft example

Warm return · Water brings heat from the chiller condenser to the top of this example tower.

Normal operation

Example training conditions

  • Hot condenser water reaches the tower at 92°F and returns to the chiller at 82°F. Range is 10°F.
  • At 75°F entering-air wet-bulb, approach is 7°F. Weather, load, flow and tower condition affect these values.

Worked service example

Leaving tower water is 4°F warmer than yesterday.

Recorded field evidence · training example

  • Yesterday 77°F cold water with 70°F entering wet-bulb.
  • Today 81°F cold water with 74°F entering wet-bulb.
  • Condenser load and flow have not yet been compared.

Approach was 7°F on both days. The weather change can account for the warmer supply, but a capacity comparison also needs load and flow. Check both before changing the tower control.

Terms in this lesson
Wet-bulb
Temperature associated with evaporative cooling of a wetted sensor exposed to airflow.
Approach
Tower cold-water temperature minus the entering-air wet-bulb temperature.

Hands-on exercise

Check a proposed cold-water target on a humid afternoon.

Predict before inspection

How does a rising wet-bulb typically affect attainable cold-water temperature at the same load and tower condition?

Knowledge check

Pass at 80%.

1. Hot water 95°F, cold water 83°F. Calculate range.
2. Where does tower water go after leaving the basin in this system?
3. Cold water 80°F and wet-bulb 74°F. Calculate approach.
4. What supplies much of the cooling in an evaporative tower?
5. Choose the strongest fair comparison of tower performance.

Field takeaways

  • Record hot water, cold water, entering wet-bulb and load together.

References and further reading