Level 1 · Commercial HVAC equipment anatomy

Follow air through a variable air volume terminal

12 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Locate the inlet, damper and outlet on VAV-01.
  • Use terminal airflow and discharge temperature to separate two delivery problems.
Before you start · 1 related lesson0 of 1 prerequisites demonstrated. You can open this lesson at any time.

What the equipment does

A variable air volume (VAV) terminal adjusts how much centrally supplied air reaches a zone. A movable blade called a changes resistance to flow. The terminal controller compares a flow measurement with a target and adjusts the damper. Some terminals have a downstream coil.

Follow the physical path

In the conference terminal, cooling air enters from AHU-01. A flow pickup senses a pressure difference that is converted to airflow using a calibrated relationship. Air passes the damper and the reheat section and leaves for the room. A fully open damper can still have little air if inlet pressure is low.

Follow the equipment pathsSelect a component to inspect its function.

Primary air · example reheat terminal

Central supply · The air handler supplies conditioned primary air through the trunk.

Normal operation

Example training conditions

  • Cooling call, target 450 cfm, measured 445 cfm, inlet air 55°F, outlet air 56°F, reheat off.
  • During a separate reheat call, the terminal can supply warmer air while holding its specified minimum flow.

Worked service example

The conference zone is hot with a full-open damper command.

Recorded field evidence · training example

  • Airflow target 500 cfm, terminal indication 160 cfm.
  • Independent outlet airflow 155 cfm; neighboring terminal meets target.
  • No direct blade observation has been made.

Two flow measurements confirm a branch shortage. Compare actual blade position with the request and inlet pressure with the design condition. The command does not identify which factor limits flow.

Terms in this lesson
Damper
A blade or set of blades that changes resistance in an air path.
Reheat
Adding heat at a terminal after the central system has conditioned the air.

Hands-on exercise

Inspect VAV-01 during a warm-room complaint.

Predict before inspection

With airflow on target, what could still make the terminal deliver excessive heat?

Knowledge check

Pass at 80%.

1. What changes first when this VAV damper moves?
2. Which comparison shows reheat effect at steady flow?
3. A terminal sensor says 0 cfm but a hood reads 360 cfm. Which path needs examination?
4. What would low supply pressure tend to do at full damper opening?
5. Target 550 cfm, measured 425 cfm. Find the shortfall.

Field takeaways

  • Compare target, actual flow, blade travel and inlet pressure before blaming the controller.

References and further reading