Level 1 · Commercial HVAC equipment anatomy

Separate the two air paths in a rooftop unit

12 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Identify the indoor supply and condenser air paths.
  • Verify cooling across the occupied-air section.
Before you start · 1 related lesson0 of 1 prerequisites demonstrated. You can open this lesson at any time.

What the equipment does

A packaged rooftop unit (RTU) houses several components in one outdoor cabinet. The training unit uses mechanical refrigeration to cool building air. Its indoor blower circulates air into the duct. Its separate outdoor fan moves air across a coil that releases heat outdoors.

Follow the physical path

Trace room return and outdoor ventilation air into the mixing section. Follow the mixed air through the filter and indoor coil to the supply duct. Outside this duct path a second stream cools the condenser and returns outdoors. In suitable weather some units use more outdoor air for cooling, a strategy called economizing.

Follow the equipment pathsSelect a component to inspect its function.

Supply air · example packaged unit

Outdoor heat rejection

Intake · In this example a rooftop mixing section admits outdoor air.

Normal operation

Example training conditions

  • During mechanical cooling with the blower running, mixed air 77°F becomes 58°F supply air.
  • Outdoor air entering the condenser at 88°F leaves that section warmer. The condenser exhaust remains outdoors.

Worked service example

A roof observer sees a turning fan and reports the room must be receiving air.

Recorded field evidence · training example

  • Condenser fan rotates.
  • Supply blower status unavailable. A calibrated hood measures 0 cfm at the affected outlet.
  • Other outlets have not been checked.

The roof observation concerns a different air stream. The outlet measurement establishes local loss of delivery. Inspect supply blower status and additional branches to distinguish a unit-wide loss from a local blockage.

Terms in this lesson
Packaged unit
Equipment assembled together in one cabinet.
Condenser
Heat exchanger where refrigerant rejects heat and condenses.

Hands-on exercise

Read the two air paths during a rooftop cooling request.

Predict before inspection

Which fan would directly move air into the supply duct?

Knowledge check

Pass at 80%.

1. Where does the outdoor condenser discharge its air?
2. An economizer can use which resource when conditions permit?
3. Mixed air 76°F, supply air 59°F. Find the drop.
4. A supply fan command is on. Which evidence verifies volume?
5. Which readings best establish cooling across the occupied-air section?

Field takeaways

  • Identify which fan and which air stream a measurement actually describes.