What you’ll learn
- Trace occupied and setback calls through an AHU or packaged RTU.
- Identify the first failed transition using command, motor proof and measured airflow.
Before you start · 3 related lessons
0 of 3 prerequisites demonstrated. You can open this lesson at any time.What starts the sequence
An occupied schedule requests the building's normal temperature and ventilation service. An unoccupied zone may still call for setback heating or cooling. Draw a separate line for the enable, the effective fan The effective instruction issued to a device. Compare it with actual travel, rotation or flow. and the independent run indication. A maintained run command can reach a drive that has no permission to run. A proven motor can turn a broken belt while the wheel remains stationary.
What changes after air is established
In a hydronic air handler, normal airflow allows the temperature loop to modulate its coils. A packaged RTU commonly uses a compressor stage and a local controller with airflow, temperature and timing permissives. On an economizing call the dampers may deliver enough cooling to avoid a compressor start. A waiting stage is a useful observation only when compared with demand, the remaining delay and the local A condition the sequence requires before an action, such as a ready input before a fan start. status.
Choose a measurement with a physical consequence
Check the source of each An observation satisfying a defined criterion. A current switch proves current above its threshold. A duct switch proves pressure differential at its taps. point on the controls submittal. A drive run relay indicates drive state. A duct switch responds to its pressure differential and a flow station estimates delivered volume. Compare the indication with a field observation, then follow the first transition that failed. Leave freeze protection and local safety limits in service throughout the investigation.
- Occupancy or setback call
- Effective fan command
- Fan rotation and duct airflow
- Economizer or mechanical cooling
- Discharge temperature response
Normal operation
Example training conditions
- At occupied start the controller requests the supply fan. On this example unit the drive accepts the start, speed increases and the airflow proving switch closes 8 seconds later.
- Coil operation follows the sequence's required proof and other permissives. Record each change in order.
Worked service example
An RTU appears enabled during morning occupancy but gives warm supply air.
Recorded field evidence · training example
- Zone 79°F, cooling target 74°F
- Supply fan requested on, run proof off
- Supply airflow 0 cfm, compressor proof off
The first missing response is fan operation. The silent compressor is consistent with loss of airflow permission. Investigate the fan run circuit before evaluating refrigeration capacity.
Field procedure
- Read the active occupancy mode and target at the event time.
- Compare the effective run request with drive status, fan proof and actual airflow.
- After airflow recovers, observe the subsequent cooling stage and discharge temperature.
Hands-on exercise
Keep cooling demand active and remove a fan permission. Trace the first transition that cannot complete.
Occupied start sequence
This training sequence releases the coil at 15 seconds if fan proof is present. Separate the run request, drive permission, measured fan response and coil release.
Capture a start request with the drive unavailable. Restore drive availability, then advance until proof releases the coil.
Unit 4 service call
The operator enabled the AHU. Should the fan have started yet?
Predict which transition is permitted and when its proof timer starts. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
RTU-01 operating cutaway
Locate the mixed-air and blower sections. Compare the fan request, fan proof, delivered airflow and first-stage proof in the point list.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Capture request, permission, proof and physical response on one timeline.
- Enable status alone cannot establish a refrigeration fault.